Helios-P Drucksensor Payload Decoder LoRaWAN®
function decodeUplink(input) {
function uncomplement(val, bitwidth) {
var isnegative = val & (1 << (bitwidth - 1));
var boundary = (1 << bitwidth);
var minval = -boundary;
var mask = boundary - 1;
return isnegative ? minval + (val & mask) : val;
}
var decoded = {};
var bytes = input.bytes;
if(input.fPort == 1){// TELEMETRY
//decode header
decoded.base_id = bytes[0] >> 4;
decoded.major_version = bytes[0] & 0x0F;
decoded.minor_version = bytes[1] >> 4;
decoded.product_version = bytes[1] & 0x0F;
decoded.up_cnt = bytes[2];
decoded.battery_voltage = ((bytes[3] << 8 ) | bytes[4]) / 1000.0;
decoded.internal_temperature = bytes[5] - 128;
// Reason of this uplink
// reasonRaw & 0x01 -> Regular send period
// reasonRaw & 0x02 -> Measured delta exceeds threshold
// reasonRaw & 0x04 -> Critical Alarm, Temperature or Pressure critical
decoded.reasonRaw = bytes[6];
// One ore more alarms
// alarmRaw & 0x01 -> Pressure low
// alarmRaw & 0x02 -> Pressure high
// alarmRaw & 0x04 -> Pressure critical
// alarmRaw & 0x10 -> Temperature low
// alarmRaw & 0x20 -> Temperature high
// alarmRaw & 0x40 -> Temperature critical
decoded.alarmRaw = bytes[7];
// Pressure reading status
// OK = 0 (No Problems)
// ERROR_PROBE = 1 (Probe not working correctly or not connected)
// ERROR_ADC = 2 (Problem with adc on helios board)
// ERROR_VALUE = 3 (Measured Value out of range, probe or board issue, try differnt probe)
decoded.status = bytes[8];
// Pressure in mBar
decoded.pressure = bytes[9] << 8 | bytes[10];
}
return {
data: decoded,
warnings: [],
errors: []
};
}
Revision Table - Dokumentenhistorie
Datum |
Beschreibung |
01.03.2023 |
Erstellung |
|
|
|
|
|
|
|
|
|
|
|
|